ROBERTSON VENTILATION INTERNATIONAL
Exhaust Systems
Smoke/Heat Release (ARV)

Coefficient of Discharge: 0.78

The Robertson ARV is designed to automatically provide its maximum exhaust area under fire conditions, whilst providing a fully weathered unit in its normally closed position.


Typical Cross Section

Design features

  • Coefficient of Discharge: As determined by independent tests is a minimum of 0.78. This result is based on tests of the largest ARV unit and were carried out in accordance with international standards.
  • Maintenance testing: Regular maintenance testing of all automatic smoke/heat release ventilators is a standard building code requirement. ARV Ventilators incorporate the necessary facilities to enable this testing.
  • Remote control systems: Can be provided with electrical or pneumatic remote control systems with zone control if required.
  • Base types: Available with a Type A, Type B (to fit a soaker sheet), or Type C (curb fixing base).
  • Materials: Can be supplied in a wide range of cladding materials including Versacor coated sheeting.
  • ARV vents are designed to meet international building code standards.
Penfolds Winery, Sth Australia

ARV Ventilators
Penfolds Winery, South Australia

Smoke/Heat Release Systems

To establish the most effective fire ventilation systems, Robertson in Australia has participated in several research programs, including a full scale Federal Government project in which 111 experiments were conducted in a study coordinated and managed by the CSIRO in an aircraft hangar in Darwin.

In 1978, Robertson was invited to participate in the formulation of the Standards on Smoke/Heat Release Vents, conducted by the Australian Standards Committee. By choice, all products developed by Robertson since the inception of the Standard comply with the requirements of AS2427-1983 and other international standards.

It should be noted that while all Robertson Smoke/Heat Release Ventilators have been designed, manufactured and tested to all current and relevant Australian Standards, these products are constantly reviewed in the light of any pertinent international standards.

 

Dimensions and Mass:
Unit
Aerodynamic Free Area
m2
Dimensions (mm)
Mass
A
B
C
D
E
F
G
Versacor
Zincalume
Aluminium
1210
0.84
1300
1200
1700
1500
310
1100
1000
46
37
25
1216
1.35
1300
1200
1700
2100
310
1700
1600
60
50
32
1222
1.85
1300
1200
1700
2700
310
2300
2200
74
62
39
Back to Top

 

Click link to download Acrobat pdf data sheet
Smoke/Heat Release (ARV) Ventilators

83 KB

Contact your nearest RVI service centre for performance details and technical advice.