ROBERTSON VENTILATION INTERNATIONAL
Inlet Systems
Acoustic Louvres

Series 7000 Type 7010
Series 7000 Type 7020
Series 7000 Type 7030
Series 7000 Type 7040

Series 7000 - Type 7010
The Robertson Acoustic Louvre Type 7010 is a factory assembled, medium performance, half chevron louvre. The following are noise reduction levels (in dB) recorded during testing.

Series 7000 - Type 7020
The Robertson Acoustic Louvre Type 7020 is a factory assembled, medium performance, full chevron louvre. The following are noise reduction levels (in dB) recorded during testing.

Typical Cross Section
Type 7010

Typical Cross Section
Type 7020

Standard Height
No of Intermediate
Blades
Types 7010 & 7020
*2
590
3
740
4
890
5
1040
6
1190
7
1340
8
1490
9
1640
10
1790
11
1940
12
2090
13
2240
14
2390
15
2540
* Denotes minimum dimensional limitation
NOTE: Standard heights shown give maximum free inlet area, however louvres can be manufactured to suit any opening dimension.

Frequency
(Hz)

Noise reduction (dB)
Type 7010
Type 7020
63
8.5
9.5
125
11.5
11.5
250
10
16.5
500
14.5
21.5
1K
21
39
2K
23.5
35.5
4K
24
38
NOTE: Tests were carried out in accordance with ASTM E336-67T, Section A2.3 Test Procedure for Measuring Transmission Loss in Non-Laboratory Type Configuration. The field transmission loss is determined as specified in Section A2.3 E.336, and is defined as follows: FTL = NR - 6.

Acoustic Inlet Louvres
Newport Power Station, Australia


Series 7000 - Type 7030
The Robertson Acoustic Louvre Type 7030 is a factory or site assembled, medium to high performance, half chevron louvre. The following are noise reduction levels (in dB) recorded during testing.


Series 7000 - Type 7040
The Robertson Acoustic Louvre Type 7040 is a factory or site assembled, high performance, half chevron louvre. The following are noise reduction levels (in dB) recorded during testing.

Typical Cross Section
Type 7030
Typical Cross Section
Type 7040

Frequency
(Hz)

Noise reduction (dB)
Type 7030
Type 7040
63
8
12.5
125
15.5
24
250
18
24
500
26
31.5
1K
35.5
36.5
2K
37
39.5
4K
33
34
NOTE: Tests were carried out in accordance with ASTM E336-67T, Section A2.3 Test Procedure for Measuring Transmission Loss in Non-Laboratory Type Configuration. The field transmission loss is determined as specified in Section A2.3 E.336, and is defined as follows:
FTL=NR-6.
Standard Height
No of Intermediate
Blades
Type 7030
Type 7040
*2
1730
1172
3
2030
1507
4
2330
1846
5
2630
2183
6
2930
2520
7
3230
2857
* Denotes minimum dimensional limitation
NOTE: Standard heights shown give maximum free inlet area, however louvres can be manufactured to suit any opening dimension.
Back to Top
Click link to download Acrobat pdf data sheets

Acoustic Louvres, Type 7010 & 7020
Acoustic Louvres, Type 7030 & 7040

80 KB
57 KB
Contact your nearest RVI service centre for performance details and technical advice.